Static Grounding Monitoring System MODEL: SLA-S-Y

SKU: SLA-S-Y

The "Static Grounding Monitoring System" functions as a part of an Overfill Protection & Earthing System. These provide a visual green light indicating a confirmed grounding condition of road tanker vehicles during the transfer of flammable and combustible materials. A red light indicates the absence of dependable grounding. An interlock circuit inside the control panel will prevent pumps and equipment from starting until a satisfactory ground is established. The interlock circuit will also shut off pumps and equipment if the ground is lost during the pumping operation.

Chia sẻ:
Input Power: 85 VAC to 250 VAC 50 Hz
Input Current: <60m A 
Output Signal: On-Off signal 
Monitoring Set Point: 10 ohms 
Alarm: Visible alarm 
Spiral Cable: Extendable to 5.3 m (17.4 ft.)
Output Safety Parameters:
Um:250 VAC, Uo: 14.28 VDC, Io: 27.2 mA, Po:97 mW,Co:4.17μF, Lo:192mH
Indicator: Lamp (Green=satisfactory ground and red=no ground)
Ambient Temperature: -20℃ to +55℃(-4℉ to +131℉)
EU-Type Examination Certification No.: Presafe 16 ATEX 8909X
QAN Certificate No.: Presafe 16 ATEX 7744Q
Standard: EN60079-0, EN60079-1, EN60079-11
Applicable Directive:2014/34/EU
Categories Static Grounding Monitoring System
Brand ALPTEC Static Grounding Solutions Manufacturer
Model SLA-S-Y
Structure Controller+ Grounding Cable
Controller Material Aluminum
Cable Length 5m 7m 10m
Cable Material Copper
Certification ATEX cert.