GB/T3836.1、GB/T3836.2、IEC60079-0、IEC 60079-1、EN60079-0、EN60079-1

| Explosion-Proof Marking | Rated Voltage (V) | Rated Current (A) | Applicable Category | Compatible Terminal Cable |
|---|---|---|---|---|
| Ex db IIC T6 Gb | AC/DC 12-36, AC/DC 48-127 AC 220-415V, DC 220-250V |
6(-20+70℃) 6(-20+60℃) |
AC12, AC15 DC12, DC13 |
2.5mm² |
1. This device consists of two parts: the button core body and the button head assembly;
2. The button head is injection molded from high-quality imported engineering plastic and chrome-plated metal or stainless steel;
3. This device is designed for use with all explosion-proof enclosures manufactured by our company;
4. It must not be used independently in explosive gas environments;
5. Installation is top-mounted.



1. Suitable for Zone 1 and Zone 2 locations in explosive gas environments;
2. Suitable for Class IIA, IIB, and IIC explosive gas environments;
3. Suitable for Zone 21 and Zone 22 locations in explosive dust environments;
4. Suitable for Class IIIA, IIIB, and IIC explosive dust environments;
5. Suitable for temperature classes T1 to T6;
6. Suitable for hazardous environments in petroleum extraction, refining, chemical processing, power generation, offshore oil platforms, oil tankers, painting, metalworking, and similar applications.